Voltage DC | |
Maximum Voltage | 1000 V |
Accuracy | ±(0.09%+2) |
Maximum Resolution | 0.001V |
Voltage AC | |
Maximum Voltage | 1000 V |
Accuracy | ±(2%+3) |
AC Bandwidth | 5kHz with low pass filter; 3db @ 800 Hz |
Maximum Resolution | 0.1 mV |
Current DC | |
Maximum Amps | 400mA |
Amps Accuracy | ±(0.2%+2) |
Maximum Resolution | 0.01 mA |
Current AC | |
Maximum Amps | 400mA |
Amps Accuracy | ±(1.5%+2) 1kHz bandwidth |
Maximum Resolution | 0.01 mA |
Resistance | |
Maximum Resistance | 50 MΩ |
Accuracy | ±(0.9%+2) |
Maximum Resolution | 0.1Ω |
Capacitance | |
Maximum Capacitance | 9,999 μF |
Accuracy | ±(1.2%+2) |
Maximum Resolution | 1 nF |
Frequency | |
Maximum Frequency | 100 kHz |
Accuracy | ±(0.1%+1) |
Maximum Resolution | 0.01 Hz |
Temperature Measurement |
-40.0 °C to 537 °C -40.0 °F to 998 °F excluding probe |
Diode Test | |
Range | 6 V |
Resolution | 1 mV |
Accuracy | ±(2 % + 1) |
Insulation Test | |
Minimum Test Current @ 1kΩ/V | 1mA |
Test Voltages | 50, 100, 250, 500, 1000 V |
Maximum Resistance per Test Voltage | 100V: 2 GΩ |
Maximum Resolution per Test Voltage |
50V: 0.01 MΩ 100V: 0.01 MΩ 250V: 0.1 MΩ 500V: 0.1 MΩ 100V: 0.1 MΩ |
Accuracy per Test Voltage |
50V: ±(3 % + 5) 100V: ±(3 % + 5) 250V: ±(1.5 % + 5) 500V: ±(1.5 % + 5) 100V: ±(1.5 % + 5) to 600 MΩ, ±(10 % + 3) above 600 MΩ |
Environmental Specifications | |
Operating temperature | ?20 °C to +55 °C |
Storage temperature | -40°C to +60°C |
Humidity (Without Condensation) |
0% - 95% (10 °C – 30 °C) 0% - 75% (30 °C – 40 °C) 0% - 40% (40 °C – 55 °C) |
Operating Altitude | 2000 m |
Safety Specifications | |
Overvoltage category | Complies with ANSI/ISA 82.02.01 (61010-1) 2004, CAN/CSA-C22.2 NO. 61010-1-04, and IEC/EN 61010-1 2nd Edition for measurement CAT III 1000 V and CAT IV 600 V |
Agency Approvals | 2000 m CAT III 1000 V, CAT IV 600 V; 3000 m CAT II 1000 V, CAT III 600 V |
Mechanical & General Specifications | |
Size | 203 x 100 x 50 mm (with holster) |
Weight | 624 g |
Warranty | 3 years |
Battery life Alkaline | Meter use 1000 hours |
Insulation test use | Meter can perform at least 1000 insulation tests with fresh alkaline batteries at room temperature. These are standard tests of 1000 V into 1 MΩ with a duty cycle of 5 seconds on and 25 seconds off. |
IP Rating | IP40 |
Fluke i400 | |
Nominal current range | 400A |
Continuous current range | 1 A - 400 A |
Maximum Non-Destructive Current | 1000 A |
Lowest measurable current | 1 A |
Basic accuracy |
2% + 0.06 A (45-400 Hz) (% reading + floorspec) |
Useable frequency | 5 Hz - 20 kHz |
Output level(s) | 1 mA/A |
Safety Specifications | |
Safety | CAT IV 600 V, CAT III, 1000 V |
Maximum voltage | 1000 V AC rms from earth to ground, in compliance with EN61010 |
Mechanical & General Specifications | |
Warranty | 1 year |
Maximum conductor diameter | 32 mm (1.25 inches) |
Maximum conductor size (busbar) | 750 MCM |
Output cable length | 1.5 m (59 inches) |
Shrouded banana plugs | Yes |
Fluke 62 | |
Backlit display for use in poorly lit areas | Yes |
Holds temperature readings | Yes |
Range | -30 to 500 °C (-20° to 932 °F) |
MIN/MAX/AVG | MAX |
Datalogging | N/A |
Distance to spot ratio | 10:1 at 80% energy |
Hi-Lo Alarm | N/A |
Optional RTD probe (contact temperature measurement) | N/A |
Emissivity | Fixed at 0.95 |
Measurement Accuracy |
10 °C to 30 °C (50 °F to 86 °F) : ± 1 °C (2 °F) Outside 10 °C to 30 °C (50 °F to 86 °F) : ± 1.5 °C (3 °F) or ± 1.5 % of reading, whichever is greater |
Includes
Fluke 1587 Insulation Multimeter
Fluke i400 AC Current Clamp
Fluke 62 Mini IR Thermometer
Rugged, utility hard case to carry everything
SIÊU THỊ THIẾT BỊ ĐO QUANG MINH - CÔNG TY TNHH ĐẦU TƯ VÀ TT QUANG MINH
ĐT: 04.3873.0880 - Hotline: 090.400.3848 - Fax: 04.3873.0880
Email: kd@sieuthithietbido.com - Website: www.sieuthithietbido.com - www.sieuthithietbidienmay.net